UofL Wiring Standards
The
Contents
Section 1 -
Service Entrance and Termination – Outside Plant
1.1 Overview
1.2
Entrance cable
1.3
Conduit
1.4
Manholes
1.5
Drawings
Section 2 –
Telecommunications Rooms and Cable Termination
2.1
General
2.2
Requirements
2.3
Cable
2.4
Racks and Panels
2.5
Wire Dress
2.6
Voice/Data Rack and Patch Panel
Section 3 –
Communication Outlets – Inside Plant Wiring and Raceways
3.1
General
3.2
Communication Outlet Location
3.3
Communication Outlet Installation
3.4
Wiring Pathways
3.5
Conduit
3.6
Cable Trays
3.7
Open Top Cable Support and Rings
3.8
Under-floor Duct Systems
Section 4 –
Television Cable
4.1 General
4.2
Video/Projection Devices
4.3
High Tech Classrooms
Section 5 –
Protection, Grounding and Bonding
5.1 Lightning Protection
5.2 Grounding
5.3 Bonding
Section 6 – Inspection, Testing and Documentation
6.1 Inspection of Work
6.2 Testing
6.3 Documentation Standards
Section
7 – Fire Stopping
7.1 General
Section 8 – Local
Area Networks
8.1 General
8.2 Determining Requirements
8.3 Wiring Type
Section 9 - Wide Area Networks
9.1 System Design
Section 10 – Low
Voltage Cable Technology
10.1
Overview
10.2
Fiber Optic Cable
10.3
UTP
10.4
Coaxial
10.5
Specifications
Section 11 – Miscellaneous and Special Situations
11.1 General
11.2 Wireless LAN connectivity
Section 12 – Codes, Standards, and Regulations
12.1 General
12.2 Agencies
Section 13 – Standardized Equipment
13.1
Standardized Solution
Section 14 –
Communication Services Information
14.1
General
14.2
Contacts
Section 1 - Service
Entrance and Termination - Outside Plant
1.1
OVERVIEW
1.2
ENTRANCE CABLE
1.3
ENTRANCE CONDUIT
1.4
MANHOLES
1.5
DRAWINGS
1.1
OVERVIEW
This
section provides the necessary guidelines to install service entrance cables to
buildings and information for the termination of cables entering buildings.
All
outside plant voice, data, video cabling, communication conduits and manholes,
shall be designed and/or approved by the University's Department of Information
Technology Communication Services (ITCS).
1.2
ENTRANCE CABLE
1.2.1
GENERAL
Prior
approval and coordination with Information Technology Communication Services,
and concerned parties is necessary when a situation requires pulling cable
through any communications conduit.
All
building entrance cables associated with campus telecommunication networks
(telephone, data, LAN, WAN, campus TV, and fiber optics) shall be installed,
connected and disconnected by Information Technology Communication Services or its
designee.
All
trunk cables requiring splicing will be performed in accordance with current
industry standards. In most cases, trunk cabling is to be installed in a
building-to-building manner leaving no splice cases in communication manholes,
tunnels or duct systems.
There
shall be no cable or wiring with voltages higher than 90 volts AC in
communications duct banks.
Note:
Hard-line coax cable for backbone CATV networks may carry voltage as high as 90
VAC.
All
twisted pair cables entering a building shall be terminated on protection
blocks. Only gas and/or solid state protectors shall be used. See protection specifications
in Section 5.
Repair
or replacement of damaged cable is the responsibility of the party involved
causing the damage. This will be done at no cost to the University. Information
Technology Communication Services must inspect and approve all repairs to
damaged cables. All damages shall be reported immediately to Information
Technology Communication Services (502-852-5145). University Planning, Design
and Construction (502-852-6176), and Physical Plant (502-852-6245) must also be
notified about damage(s) due to activities of project contractors under their control.
1.2.2
LABELING
All
trunk cables installed in manholes shall be identified as to the owner of the
cable, cable number, cable type, number of pairs or strands, origination and
termination points and contact number (502-852-5145). The information on the
tag shall be in permanent ink encased in a waterproof tag made of plastic or
other such material designed to be used in a wet environment. Or, tag may be
plastic or aluminum with information stamped or embossed. A tag is required at each end of the cable
and at all pull points in between.
All
abandoned communications cable shall be removed from tunnels, manholes and
conduit. If it is not feasible to remove abandoned cable, it shall be clearly
tagged as abandoned, with appropriate labeling as described above, and shall be
reported to Information Technology Communication Services and Physical Plant.
1.2.3
AERIAL
No
aerial wiring shall be installed on campus unless approved by the Information
Technology Communication Services. Information shall be obtained from
Information Technology Communication Services in reference to ownership of
aerial communication cables and poles.
1.3
ENTRANCE CONDUIT
1.3.1
GENERAL
Conduit
sizing and quantities for communications conduits between buildings and
manholes shall be determined by Information Technology Communication Services.
Minimum requirements are outlined in the following paragraphs.
All
campus buildings shall be connected to the nearest manhole/tunnel or new
manhole/tunnel. Connection to a tunnel is detailed in section 1.3.4. Fireproof
seals shall be required by code as detailed in Section 7.
Prior
approval and coordination with Information Technology Communication Services,
and other concerned parties is necessary when the situation requires any
modification to the conduit system.
Repair
or replacement of damaged conduit is the responsibility of the party involved
causing the damage and at no cost to the University. Information Technology
Communication Services must review and approve all repairs to damaged
communications conduits. All damages shall be reported to Information
Technology Communication Services and Physical Plant immediately.
1.3.2
REQUIREMENTS
The
minimum size duct bank for entrance conduit to a new building shall be (4) four
inch conduits with innerduct. Whenever feasible, buildings larger than 100,000
square feet shall have two means of access to the campus underground
communications conduit system.
Two
of the four inch conduits will each contain a flexible, multi-cell, textile
innerduct. This innerduct will be a 3” x (3) cell configuration with a detectable
tracer. Each cell will have a color coded mule tape with distance markers. The
mule tape is to be tied off at each end. The flexible innerduct must be pulled
with the use of a swivel head pulling eye as to prevent twisting of the
innerduct. The other (2) four inch conduits will only contain a mule tape with distance
markers extended through the entire length of each conduit. There shall be no
splices or knots in the length of the mule tape. The mule tape is to be tied
off at each end.
No
more than the equivalent of 180 degrees of bends is allowed in a run between
the building and the manhole, including offsets.
All
existing conduits require a flexible, multi-cell, textile innerduct installed
prior to any cabling being pulled into the conduit. The flexible innerduct must
be pulled with the use of a swivel head pulling eye as to prevent twisting of
the innerduct.
Conduits
with an inner diameter of less than 3 inches require a textile innerduct 1 inch
to 1¾ inches wide. Each cell is to have a mule tape with distance markers. The
mule tape is to be tied off at each end. The flexible innerduct must be pulled
with the use of a swivel head pulling eye as to prevent twisting of the
innerduct.
1.3.3 UNDERGROUND
All
underground conduits and ducts shall be added in groups of 2 or more. Under no
circumstances are single underground conduit runs acceptable without specific
permission from IT Communication Services.
All
underground conduits shall be configured in what is commonly known as a duct
bank that is encased in concrete (3500psi minimum) reinforced with steel rebar.
Additional reinforcement is to be used when crossing roadways.
The
minimum separation for communications ducts and power ducts in a joint trench
environment is 3 inches (8 cm) of concrete. All communications ducts shall also
be a minimum of 12 inches from steam pipes and condensation lines when crossing
perpendicular. The minimum depth for buried conduit and ducts is 30 inches
below grade or underside of road bed to top of duct/conduit.
When
communication ducts run parallel to steam lines a minimum of a two (2) foot
separation is required to avoid conduction of heat. PVC duct is not allowed in
steam tunnels. All other duct separations must comply with the National
Electric Code.
Rigid
steel conduit, encased in reinforced concrete, shall be used in any location
subject to excessive heavy weight, such as under foundations or roadways.
All
underground communications conduit shall be four (4) inches in diameter,
minimum.
All
necessary precautions shall be taken by the contractor during construction to
prevent the lodging of dirt and construction debris in all conduit, tubing,
flow duct, fittings and boxes. All conduit in floors, concrete or below grade,
shall be swabbed free of debris and moisture before innerduct is pulled. All
newly installed conduits shall be left with a mule tape or flexible,
multi-celled, textile innerduct with pull string.
All
used and unused conduits and innerducts shall be sealed to provide a watertight
fit inside and out.
Installation
of communications conduits or duct banks are prohibited under “slab-on-grade”
constructed buildings. Entrance conduits in these types of structures shall be
turned up through the slab immediately after penetration through the perimeter
foundation wall or footer into the MTR. Where the MTR is located further into
the interior of the building, conduits shall be turned up through the slab
immediately after penetration through the perimeter foundation wall or footer
and extend into a 4’ x 4’ junction box located immediately in the space or above
the first floor ceiling. The junction box must have a removable entrance cover either
facing outward or towards the floor if above the ceiling. The conduits shall
extend from the junction box to the MTR.
1.3.4
TUNNELS
Conduit
installed in tunnels must have written approval by IT Communication Services
and reviewed by Physical Plant. Unless written exception is provided by IT
Communication Services, all conduit placed in and/or sections crossing steam
tunnels shall be rigid and galvanized.
1.3.5
CONDENSATION
Duct
banks shall be pitched to drain to manholes and away from building entrances.
1.3.6
TRAPS
All
conduit, tubing, raceways, ducts and duct banks shall be installed in such manner
to insure against collection of trapped condensation. Raceway runs shall be
arranged to be void of traps.
When
conduit passes through exterior concrete walls of any facility, the penetration
shall be watertight. Provide pipe sleeves in the concrete with 1/2-inch minimum
entrance seal.
1.3.7
TYPES OF CONDUIT
Gas
pipe and water pipes shall not be used as conduit under any circumstances.
Two
types of conduit are acceptable for underground conduit systems. Project
specifications will detail the types of conduit to be used in various locations.
- Rigid galvanized steel conduit with threaded fittings -- This conduit shall be installed with reinforced concrete
casing in areas subject to heavy use.
If not concrete encased, this conduit shall be painted with two coats of coal tar base paint or have epoxy coating applied by manufacturer. - Schedule 40 PVC conduit -- This conduit shall be installed with steel reinforced concrete casing.
Rigid
steel conduits installed underground shall be field-wrapped with 0.01 inch
thick pipe-wrapping plastic tape applied with a 50 percent overlap, or shall
have a factory applied plastic resin, epoxy or two coats of a field applied
coal tar specifically made for this purpose. Where the coal tar coating method
is used, the contractor shall notify Information Technology Communication
Services prior to back filling, for inspection and approve the coating before
the conduit is covered. Field wrapping or coating shall extend to six (6)
inches above ground level where conduit is installed by a pole or side
structure or inside a pedestal.
All
conduits that extend above ground where turned up at the base of a pole or
pedestal must be encased in concrete above ground.
Duct
banks shall be rectangular and be a minimum concrete thickness of three (3)
inches around any conduit. The duct bank shall be sized and placed as shown on
construction documents.
A
minimum of four (4), # 4 steel reinforcing rods shall be installed in all duct
banks parallel with the conduits. Where conduit enters a building or a manhole
the re-bars must be doweled into the existing structure to prevent shearing of
the conduits in case of settlement.
All
conduits must be terminated with bell ends at the manhole, facility or other
termination point.
Duct
spacers shall be provided at a maximum of seven feet intervals. Conduit shall
be anchored at forty-two inch intervals and at each spacer to prevent duct
floating during concrete installation.
Each
duct run shall be done with a continuous concrete pour. Broken pours are not
allowed without written exception from Information Technology Communication
Services. Provide #4 or larger re-bar to
extended twelve inches beyond the end of the pour where encasements are not
completed end to end in a single pour.
A
yellow color agent shall be sprinkled on top of the concrete used for
underground communications ducts. The color agent is to comply with industry
standards. Marker tape shall be placed 12 inches above the poured concrete duct
casing.
1.4
MANHOLES
1.4.1
GENERAL
Manholes
shall not be smaller than 7 feet wide, 7 feet long and 7 feet high.
The
maximum depth of all manholes shall be ten (10) feet from the manhole cover to
bottom of the manhole, unless otherwise approved by Information Technology
Communication Services.
The
manhole cover and opening shall be round, 36 inches in diameter and shall be
engraved or embossed with the word "Communications." Manhole covers
shall not have recessed handles that pull out when needed for removal. Notched
type covers shall be used.
The
maximum distance between manholes in any continuous one run shall not exceed
400 feet.
1.4.2
INTERIOR
All
materials used in a manhole shall be resistant to corrosion. All steel shall be
galvanized or zinc coated. All racks in manholes shall be galvanized or zinc
coated steel.
1.5
DRAWINGS
1.5.1
GENERAL
Detailed
diagrams can be obtained from the University of Louisville Department of
Physical Plant or Information Technology Communication Services if available.
Refer any questions specifically not addressed in this document to Information
Technology Communication Services.
Section 2 -
TELECOMMUNICATIONS ROOMS AND CABLE TERMINATION
2.1
GENERAL
2.2
REQUIREMENTS
2.3
CABLE
2.4
RACKS AND PANELS
2.5
WIRE DRESS
2.6
DATA RACK AND PATCH PANEL
2.1
GENERAL
Telecommunication
rooms are special-purpose rooms that contain telecommunications equipment and
wiring. These rooms have specific requirements due to the nature, size and
complexity of the equipment and wiring located in the room.
2.2.1
SPACE REQUIREMENTS
There
are two different types of telecommunications rooms within a building each
supporting critical functions as part of the building voice/data/video wiring
and communications systems. In general, each room must be large enough to
accommodate the wiring and equipment that will be located within them and
reserve space for growth. The two types of rooms are:
There is normally only one MTR per
building. This room will contain data switches, routers, telecom, and video
distribution electronic equipment. This room will also serve as the primary
location for communication cabling to enter the building.
More than one TER per floor is required when the terminated wiring distance between any voice/data communications outlet and
the TER exceeds 295 feet (90 meters).
The
minimum size for a MTR is 400 square feet. The preferable dimensions for this
room are 20’X20’. This room will contain telephone equipment, data network
equipment, racks, cabinets and other approved networking equipment. Information
Technology Communication Services shall be contacted for final dimension
approval.
The
minimum size for a TER is 100 square feet and the preferable dimensions for
this room are 10’X10’. Only in approved ITCS cases shall this room be less than
100 square feet. Information Technology Communication Services must be
contacted for final dimension approval. This room will contain telephone
equipment, data network equipment and voice/data wiring.
NOTE:
Telecommunications rooms may vary in size according to the square footage of
the building, number of floors, tenant characteristics and telecommunications
services required. Consideration to the future needs of the facility and the
end users is a necessity. Information Technology Communications Services will
have final approval on room dimensions.
Both
the MTR and the TER will have sufficient lighting, HVAC, sprinkler and door access
control. In all new facilities door
access control to the MTR and the TER will be via a card reader attached to the
University’s door access control system.
Project
specifications will indicate that Information Technology Communication Services
personnel or its designee are responsible for furnishing, installing and
terminating the various types of communications cabling, racks, panels and
other items as specified in this section.
In
new construction buildings, an approved 5-pound halon type fire extinguisher
must be provided just outside the door of each room. The extinguisher is to be
enclosed in a flush mounted extinguisher cabinet with appropriate signage.
All
work shall comply with the National Electrical Code, Local Building Codes,
current 568 TIA-EIA standards and the
Electrical
panels are strictly prohibited in telecommunications rooms. Services, which are
not telecommunications related, shall also be prohibited in these rooms. This
includes, but is not limited to, janitorial services and supplies, zone
maintenance storage of supplies, tools and equipment, departmental storage of
supplies and equipment, annunciating equipment and building security network
control devices. There shall never be an exception to these restrictions. Fire
alarm and security panels are not permitted in telecommunication rooms.
A
50 percent growth factor shall be built in and provided in each riser unless
otherwise specified; consequently any cable or conduit work that pertains to
telecommunications must be designed and/or approved by Information Technology
Communication Services. Project specifications will include this growth factor.
To
facilitate proper installation, routing and placement of cables, wires, premise
equipment and terminal fields, telecommunications rooms shall be located on
each floor, as close as possible to the middle of the building and stacked one
above the other, unless otherwise instructed or approved by Information Technology Communication Services.
Architects and Engineers must pay special attention to telecommunication room
locations to overcome distance limitations relating to data networks. The total
distance of the conduit path, from outlet to the TER or MTR, when the MTR also
serves as a TER, shall not exceed 275 feet.
Every
network-attached device must be cabled back to the nearest TER or MTR on the
same floor. The telecommunication room(s) shall house all and only the
equipment directly related to the telecommunications systems.
2.2
REQUIREMENTS
2.2.1
GENERAL
All
telecommunications room doors are to be keyed alike using the MK key as
designated UofL Physical Plant. Locks shall be spring lock (self-locking or
store room type locks) and UofL Physical Plant will install locks. Only
authorized IT technicians and Physical Plant supervisors may carry a key to
these rooms.
New
facilities – All new building telecommunication rooms will be on the
University’s card key system.
Doorways
shall be designed with minimum measurements of 3’-0" by 6’-8" minimum
and shall open outward into the corridor or adjacent space.
Floors
shall be sealed concrete or tile, carpet is prohibited.
MTRs
and TERs shall be located above any threat of flooding. Rooms located in
basements shall have floor drains with positive drainage, otherwise sump pumps
must be provided. When sump pumps are required, they shall be connected to an
emergency power supply.
Fire
rated plywood, 3/4 inch thick, must be mechanically fastened to the walls
specified in the project specifications of each MTR and TER. The fire rated
plywood must be fastened in a way that is easily removable. The fire rated
plywood shall be painted with two (2) coats of fire resistant paint of a
neutral color. The fire rated plywood is to begin at four (4) inches AFF (above
finished floor) and end at 8’-4" AFF.
The
recommended ceiling height is minimum 8’-6".
Install
a minimum of 4 (four) 4 inch sleeves between telecommunications rooms, with
sleeves extended 4 (four) inches AFF. In buildings with Plenum rated ceilings,
EMT multi-cell conduit shall be used to connect telecommunication closets
together. Buildings taller than 4
stories shall require an increase in the minimum number of sleeves as follows:
5-8
stories - 8 sleeves floors 1-4, 4 sleeves floors 5-8
9-12 stories - 12 sleeves floors 1-4, 8
sleeves floors 5-8, 4 sleeves floors 9-12
2.2.2
ENVIRONMENT
All
telecommunications rooms shall be environmentally controlled to maintain the room
environment at a temperature range of 65 to 75 degrees Fahrenheit, with a
relative humidity level of 35 to 75 percent non-conducting, 24 hours a day, 7
days a week. Telecommunications rooms shall be conditioned with a fresh air
exchange of three (3) air changes per hour. If HVAC must be shut down then an
exhaust connected to emergency power must be provided to remove heat. Generally
the system must remove 7,000 BTU per hour.
No
plumbing, HVAC ducts, or electrical conduit shall pass through or be directly
above any telecommunications room.
2.2.3
ELECTRICAL
Lighting
shall be four (4) foot fluorescent type and provide a minimum of 50 FC at 3
feet above the floor and be connected to the emergency generator when
available.
A
minimum of 2 double duplex AC outlets must be provided to power telephone
system components, computer interfaces, network electronics and other
telecommunications requirements. Outlets must be flush when cut through
plywood. Outlet locations will be determined during the building design stage.
Each
double duplex outlet shall be connected to a dedicated circuit breaker. Each
dedicated electrical circuit shall be 20-amp, 110V, 60 HZ type. All circuits
must be tied to an emergency generator when available. All outlets shall be
labeled with panel and circuit location.
All
breaker panels are to be labeled and identified to avoid being turned off in
error. Breakers servicing the MTR or TER shall be equipped with locking devices
to prevent turn off. A minimum of 2 (four) 20-amp circuits are to feed each
room.
2.2.4 GROUNDING
All
MTRs and TERs shall have a grounding bar, which shall be 1 foot long for the
TER and 2 feet long for the MTR. Both shall be 4 inches wide by 1/4 inch thick
with pre drilled NEMA bolthole sizing and spacing. This bar shall be attached
to the main building grounding system with a wire not smaller than #6 AWG
copper. The ground wire shall not share the cable tray with communications
cabling. It may be installed in a separate conduit, which may be attached to
the outside of the communications cabling cable tray.
Each
distribution point shall be grounded to the main building ground, NEC and
EIA/TIA 607 requirement shall be followed.
2.2.5 LABELING
Communications,
computer and CATV conduit is to be clearly identified, at every junction box,
via a painted section or by use of conduit stickers indicating each conduit
run; Green = computer and telephone, Yellow = CATV, Orange = fiber optic.
All
Telecommunication Equipment Room Frames, Main Cross-connect Frames and connecting
blocks must be properly identified by destination.
All
riser cables shall be properly marked with “from and to” indicators. Marker is
to be a flat piece of aluminum or wire tied plastic labels. This marking shall
be permanent and indicate:
The Origination (Cable it is feeding
from MTR #) to
The Destination (TER# it is
feeding).
All
pairs of the entrance cable must be terminated on a connecting block and
identified.
2.3
CABLE
2.3.1
GENERAL
A
50 percent growth factor shall be built in for riser cable and provided for
unless otherwise specified, consequently any cable work that pertains to
telecommunications must be designed and/or approved by Information Technology
Communication Services. Project specifications will include this growth factor.
All
riser cables that extend from the MTR to each TER must be 100 percent
terminated in the MTR and in each TER.
Plenum
or PVC communications cable may be run exposed above ceilings, provided this
cabling is supported independently of other utilities, such as conduits, pipes,
ceiling support systems, and not laid directly on the ceiling panels. PVC
jacketed cable may be used in non-plenum areas if such use meets NFPA and NEC
standards and local fire codes. PVC cable is only allowed with expressed
permission from ITCS.
To
facilitate future cable installations, a new pull string, tied off at both
ends, shall be installed in conduit simultaneously with the pull-in of cable.
All
installed station communication cables for voice and data shall be 4 pair, 24
AWG UTP, Category 5E (Enhanced), tested to 400 megahertz.
2.3.2
VOICE RISER CABLE
Voice
riser cable shall be copper, 24 AWG UTP, category 3. All station and riser
cable shall be run through and held in place with D-Rings and/or by use of wire
tray in MTRs and TERs. Terminate on 110 type IDC connecting blocks. Information
Technology Communication Services will specify Block placement and management
backboards/relay rack location. Designation strips with cable counts and jack
ID shall be installed in all cases.
2.3.3
DATA RISER CABLE
All
data riser cable will be optical fiber cable, of multi-mode and single-mode
strands. See section 2.3.4
2.3.4
FIBER OPTIC RISER
Fiber
optic riser cable shall consist of a minimum of 1 sub-unit of 12 strands of
multi-mode fiber and 1 sub-unit of 12 strands of single-mode fiber in a single
sheath. Each fiber riser shall be installed in riser-rated inner-duct (1"
I.D. min).
Termination
in the MTR and TER shall be in standard fiber optic enclosures. The multi-mode
fiber and single-mode fiber are to be terminated in it’s own enclosure. Under
no circumstances are multi-mode fiber and single-mode fiber to be housed in the
same enclosure. All fiber strands are to be terminated on ST type connectors.
2.3.5
FIBER OPTIC ENTRANCE CABLE
Fiber
optic entrance cable shall consist of a minimum of 48 strands of multi-mode
fiber and 48 strands of single mode fiber in a single sheath. The 48 strands of
multi-mode fiber shall be separated into 4 sub-units of 12 strands each. The 48
strands of single-mode fiber shall be separated into 4 sub-units of 12 strands
each.
Termination
in the MTR shall be in standard fiber optic enclosures. The multi-mode fiber
and single-mode fiber are to be terminated in it’s own enclosure. Under no circumstances
are multi-mode fiber and single-mode fiber to be housing in the same enclosure.
All fiber strands are to be terminated on ST type connectors.
2.4
RACKS AND PANELS
2.4.1
GENERAL
Each
distribution point on the MTR or TER backboard or rack shall be identified as a
building entrance and/or a floor service panel. Junction/pull boxes are to be
provided on any conduit run longer than 80 feet.
All
voice terminations at the MTR will be on standard raised 110 type-connecting
blocks, mounted on relay rack or backboards. All data terminations at the TER
will be terminated on dark red CAT 5E RJ45 jacks and inserted into QuickPort
connecting panels mounted on relay racks. Where space permits, freestanding
racks should be installed in the MTR and the TER and all terminations should be
installed on the racks.
2.5
WIRE DRESS
2.5.1
VOICE STATION WIRES
Drop
from the telecommunication cable tray, bundle and route the unshielded voice
pair groups through the backside of the 4 inch by 5 inch vertical wire management
duct to the 110 type IDC connecting blocks located on the relay rack. Organize
and label the cables in sequentially numbered order. The labels are to be
placed on the designated strip for each 110 type-connecting block.
A
single sided 1.5-inch horizontal wire management duct is to be mounted below
the 110 type-connecting block.
2.5.2
DATA STATION WIRES
Drop
from telecommunications room cable tray, bundle and route through the backside
of the 4 inch by 5 inch vertical wire management duct to the data QuickPort
panel located on the relay rack. Organize and label the cables in sequentially
numbered order. The labels are to be placed on the QuickPort panel in the
designation space for each jack.
A
single sided 1.5-inch horizontal wire management duct is to be mounted above
and below each QuickPort panel.
2.6
VOICE/DATA RACK AND PATCH PANEL
To
install network distribution panels and associated equipment use the following
installation method.
In
TERs and MTRs serving as TERs containing data terminations, mount two
freestanding relay racks in the indicated location. Position the racks to
maintain a minimum of three (3) feet clearance from the front of the rack to
the front facing room wall and three (3) feet clearance from the rear of the
rack to the rear facing room wall. If a row of racks is to be installed in a
MTR or TER, maintain a minimum of two (2) foot clearance from the rightmost or
leftmost rack to the opposing wall. Anchor racks to the finished floor. Ground
the rack to the MTR or TER grounding bus bar with #6 AWG copper wire.
Mount
the voice network riser blocks in the left most rack starting under the fiber
interface unit if one is installed. If no fiber interface unit is installed or
to be installed in the future, start at the top. Lay out the voice network
blocks in ascending serially numbered order from top left to bottom right.
When
data jacks for multiple floors are serviced out of the same TER or MTR serving
as a TER, the QuickPort panels shall be laid out and labeled as follows. *
One
or more 48 port horizontal QuickPort panels will be dedicated to each floor.
Only under specially approved circumstances shall more than one floor share a
48-port panel section. Panels will be installed with the top floor at the top
of the rack and then in descending order by floor.
Additional
racks may be required to satisfy this layout. If so, the top floor will be
located in the left rack starting again from the top of the rack and then in
descending order.
Panel
labels shall match the jack labels as described in Section 3.1.2. Each 48-port
panel section shall be labeled with the floor code letter.
The
right most rack is reserved for mounting network electronics and support
equipment.
*All
buildings constructed as of Jan. 1, 2000 shall have at least one TER on each
floor.
2.6.1
PUNCH DOWN ON SURFACE MOUNTED BACKBOARDS
Lay
down all station wire pairs in serially numbered order from lowest serial
number at the top left most position to the highest serial number at the bottom
right position. Use110 type IDC connecting blocks. Route all cables to be punched down to these
blocks starting on the left most edge down to the base of the backboard then
over and up to the block dressing the cable under the mounting legs. Fasten the
mounting brackets to the plywood backboard with #10 x 3/4 inch Phillips head
screws.
- VOICE 4-Pair -- Use 110 type IDC 100 pair 110 blocks. Locate the punch blocks on the plywood wiring surface in the area designated as Voice Station Wires. Set blocks in top/down fashion and butt adjacent to each other when installing left to right. Punch down the four (4) unshielded pairs on the block. Minimum bend radius must meet the cable manufacturer’s specifications for category 5E wiring.
- DATA 4-Pair -- Use rack mounted QuickPort patch panels. Punch down the four (4) unshielded pairs on the dark red RJ45 jack.
NOTE:
that the blocks/panels for terminating the cable may be located on the floor
above or below the floor on which the station jack is located. If this is the
case, install panels in top/down fashion. Minimum bend radius must meet the
cable manufacturer’s specifications for category 5E wiring.
2.6.2
Terminating and Cabling Standardized Products
Contact
Information Technology Facility Management (502-852-1616) for the equipment
required for all installations. Leviton communication components are the
standardized product solution for installation of voice, data and video terminating
devices. Exceptions or substitutions
must require specific needs and must be approved by Information Technology
Communication Services prior to installation.
Section 3 –
COMMUNICATION OUTLETS--INSIDE PLANT WIRING AND RACEWAYS
3.1
GENERAL
3.2
COMMUNICATION OUTLET LOCATION
3.3
COMMUNICATION OUTLET INSTALLATION
3.4
WIRING PATHWAYS
3.5
CONDUIT
3.6
CABLE TRAYS
3.7
OPEN TOP CABLE SUPPORTS AND RINGS
3.8
UNDERFLOOR DUCT SYSTEM
3.1
GENERAL
3.1.1
OVERVIEW
All
telephone, data, and CATV station cabling shall be continuous cabling from the
MTR or the TER to the communication outlet. All station cables will be free of
kinks, chafes, and tight bends. Any ceiling tiles removed by the contractor for
cable installation will be re-installed in good condition. Replacement of
damaged tiles is the contractor’s responsibility at no cost to the university.
The
building occupant's present and future requirements will determine the needs of
multiple jack outlets. Final approval for the layout of jacks shall rest with
the Information Technology Communication Services. During the programming stage
Information Technology Communication Services, consulting with the building
occupant(s), will supply the jack layout desired to the project architect for
inclusion in the project specifications.
All
analog voice connections shall terminate on black RJ-45 eight (8) conductor CAT
5E modular jack assemblies. The Quickport faceplate shall be White and will
support 4 modular jack assemblies. The voice jack color shall be Black and will
be placed in the top port(s) of the wall plate. If only one voice jack, it
should be terminated in the upper left port. Wire color-coding and termination
shall be per EIA/TIA-568-B.2 specifications. If no other jacks are to populate
the faceplate, blank modules are to be used to fill the spare positions. The
blank modules are to be the same color as the Quickport faceplate.
Analog
wall phones shall be terminated on stainless steel 630 type jack assemblies.
All
data connections shall terminate on dark red RJ-45 eight (8) conductor CAT 5E
modular jack assemblies. The Quickport faceplate color shall be White and will
support 4 modular jack assemblies. The data jack color shall be Dark Red and
will be placed in the lower port(s) of the wall plate. If only one data jack,
it should be terminated in the lower left port. Wire color-coding and
termination shall be per EIA/TIA-568-B.2 specifications. If no other jacks are
to populate the faceplate, blank modules are to be used to fill the spare
positions. The blank modules are to be the same color as the Quickport
faceplate.
All
pairs shall be terminated when connecting to voice and data jacks. Terminate as”568B”.
The
total wire path length from the data outlet to the MTR or TER termination point
must not exceed 295 feet (90 meters). This is important to meet Ethernet
requirements of IEEE 802.3. Please note that in most cases the TER that houses
network electronics will service both the voice and data jacks on the floor
where it is located. This must be considered when determining adherence to the
maximum length for the data outlet wiring.
3.1.2
LABELING
Each
end of all cables will be labeled at their termination locations.
In
newly constructed buildings communications outlets will be labeled with the
room numbers as provided on the construction documents. The format is as
follows:
Building
Acronym Room Number – Connection Count Type Connection
Where
DBB is the Building Acronym, 101 is the Room Number – Connection
Count is 1 and identifies the first connection in the room and Type
Connection D identifies the connection as a data connection. V is
to be used for analog voice connections.
The
number of connections in a room is determined by standing at the opening to the
room then start counting connections beginning with the number 1 from the
immediate left wall following in a clockwise direction around the room.
3.2
COMMUNICATION OUTLET LOCATION
3.2.1
LOCATIONS AND QUANTITIES GUIDELINES
Unless
otherwise specified, a Standard Communications Outlet (SCO) shall consist of a
voice jack, a data jack, and two spare ports.
Other communication outlets may be installed depending on the function
for that particular office or room. Quantities listed for the following areas are minimum
counts.
Faculty
Offices: One (1) SCOs per designated
occupant. If there is more than one occupant then outlets are to be installed
on opposite walls.
Clerical/Staff
Offices/Graduate Student Offices: One (1) SCO at the location of each desk.
Conference
Rooms: One (1) SCO and one CATV outlet per room for rooms up to 200 square
feet. A minimum of four (4) SCOs and two
CATV outlets per room for rooms over 200 square feet. One (1) SCO shall be
located on each wall. CATV outlets will be opposite from each other. Rooms with
more than 500 square feet shall have additional outlets equally spaced on each
wall. CATV outlet can be incorporated into a SCO spare port.
Laboratories:
One (1) SCO for each desk space and one
Classrooms/Lecture
Halls/Auditoriums: Classrooms with teaching stations are required to have two
(2) communication jacks. One designated for data, one spare. A video cable
shall also be installed at the teaching station. Classrooms without a teaching station shall
use the following guidelines for video cabling:
Number of Student CATV
Jacks Occupancy Outlets
1 1 - 15 1
2 15 - 50 2
4 50 - Over 4
NOTE: * One TV outlet in the front of room
and another in the ceiling for projection TV. If the classroom is designated as
a High Tech Classroom, then the High Tech Classroom requirements
in Section 4 may supersede the CATV outlet requirements listed above.
Residence
Hall Rooms: One (1) data communication jack per occupant or potential occupant
of each room. One (1) telephone jack per room. One (1) CATV outlet per room.
The locations will be determined during the design period of the project.
Residence
Hall Lounges: One (1) or more communication jacks and one (1) CATV outlet per
lounge. The quantity and locations will be determined during the design period
of the project.
Patient
Care Rooms: One SCO per occupant.
Storage
Areas: One (1) communication outlet per room. Two (2) outlets for rooms over
500 square feet and one (1) additional outlet for each additional 2000 square
feet.
Mechanical
Rooms: Consult the Department of Physical Plant. Some rooms may require
communications outlets for telephones or energy management devices.
MTR
and TERs: One (1) communication jack per room minimum.
3.3
COMMUNICATION OUTLET HOUSING INSTALLATION
3.3.1
MOUNTING
Use
a dual gang outlet box similar to
Use
Steel City plaster rings, part number 72-C13, (single gang) or 72-C-17 (double
gang) or their UofL approved equivalent. It is absolutely critical that the
inside opening area match the outlet installation enclosure. The plaster rings
must be level and positioned flush with the finished surface. For single
voice/data outlets use a single gang plaster ring.
Outlets
are to be mounted at standard industry heights and positions, unless otherwise
specified by the University Planning, Design and Construction and/or
Information Technology Communication Services. Standard mounting height of
communication outlets:
Desk
18 inches, AFF.
(above finished floor)
(Single gang
plaster ring)
Handicapped wall mount
48 inches, AFF.
(Single gang plaster ring only)